Medium-voltage switchgear, switchboard with load break switch
Payment Type: | L/C,T/T |
---|---|
Min. Order: | 1 Set/Sets |
Delivery Time: | 25 Days |
Packaging: | Wooden case |
---|---|
Brand: | SHFE |
Place of Origin: | Shanghai, China (Mainland) |
Supply Ability: | 300 Piece/Pieces per Month |
Basic Info
Model No.: HXGN12
Product Description
2.power Distribution Box
3.IEC 298 standard
HXGN-12 Case Type Fixed High-Voltage Vacuum Ring Main Switch Cabinet
I. Purpose & Scope of Application
The HXGN-12 high-voltage vacuum ring main switch cabinet (called ring main unit for short) is applicable to the distribution system of industrial and mining enterprises, residence communities, high-rise buildings and schools as a power supply unit of indoor three-phase 12KV, 50HZ ring main and a terminal distribution equipment. It may break or close the rated load current and Transformer no-load current, and as well break or close the capacitance current of a certain distance of overhead line, cable or condenser bank. The load switch-Fuse composite apparatus cabinet is able to break the rated short-circuit current in a one-off way and is used for protecting the equipment, distributing and controlling electric power. II. Operating environment
Ambient temperature upper limit and lower limit are respectively 40°C and -25°C;
Altitude is not more than 1000m;
Relative humidity: daily average value should not be more than 95%, while monthly average value should not be more than 90%;
Places without fire and explosion risk and violent vibration, and corrosive and combustible gas, vapor and conducting dust in the ambient air and obvious pollution.
IV. Main technical parameters
Serial No. | Item | Unit | Value | |
1 | Rate voltage | KV | 12 | |
2 | Rated current | Load switch | A | 630 |
Composite apparatus cabinet | 125 | |||
3 | Rated short-circuit making current | KA | 50 | |
4 | Rated short-circuit breaking current | KA | 31.5 | |
5 | Rated active load breaking current | A | 630 | |
6 | 4S short time withstand current | KA | 20 | |
7 | Dynamic current | KA | 50 | |
8 | 1min power frequency withstand voltage | KV | 42(fracture,48) | |
9 | Lightning impulse withstand voltage | KV | 75(fracture, 85) | |
10 | Mechanical life | Times | 10000 | |
11 | Rated take-over current (composite apparatus) | A | 3150 | |
12 | Mode of operation | Manual mode | ||
13 | Degree of protection | IP2X |
1. Scheme of primary circuit and single wire system diagram;
2. Array diagram and layout plan of ring main unit;
3. Names, specifications and quantity of electric components installed in each cabinet;
4. Operation mode of load switch and type of motor power source and operating voltage;
5. Schematic diagram of ancillary circuit;
6. Type and specification of bus bar of the primary circuit;
7. Coating color of cabinet.
Contact us if you need more details on Switchboard. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Distribution Cabinet、Control Gear. If these products fail to match your need, please contact us and we would like to provide relevant information.
Product Categories : Switchboards & Switchgears > 6,10,11kV Switchboards Switchgears