Oil immersed type 110kv 15 mva power transformer
Payment Type: | L/C,T/T |
---|---|
Min. Order: | 1 Set/Sets |
Delivery Time: | 25 Days |
Packaging: | Wooden case or packaged as customer require |
---|---|
Brand: | SHFE CHFE |
Place of Origin: | Shanghai, China (Mainland) |
Supply Ability: | 500 Set/Sets per Month |
Basic Info
Model No.: SSZ11
Product Description
Long usage life
IEC standards
Over 30 year
Original equipments manufacturer
REFERENCES ISO 1461: Hot dip galvanized coatings on fabricated iron and steel articles – Specifications and test methods. IEC 60076: Power transformers. IEC 60044: Instrument transformers. IEC 60296: Specification for unused mineral insulating oil for transformers and Switchgear. IEC 60354: Loading guide for oil – immersed power transformers. IEC 60214: Tap-changers - Part 1: Performance requirements and test methods, Part 2: Application guide. IEC 60512: Connectors for electronic equipment. Performance
110kV Two-Winding Power Transformer With NVTC/OLTC | |||||||
Rated Capacity (kVA) | Rated Voltage (kV) | Vector Group | Losses (W) | Impedance Voltage (%) | |||
HV | Tapping Range | LV | No load | On load | |||
6300 | 110 121 | ±2×2.5% | 6.3 6.6 10.5 11 | YNd11 | 8000 | 36900 | 10.5 |
8000 | 9600 | 45000 | |||||
10000 | 11200 | 53100 | |||||
12500 | 13200 | 63000 | |||||
16000 | 16000 | 77400 | |||||
20000 | 19000 | 93600 | |||||
25000 | 22400 | 110700 | |||||
31500 | 26700 | 133200 | |||||
40000 | 31800 | 156600 | |||||
50000 | 37600 | 194400 | |||||
63000 | 44600 | 234000 |
110kV Three-Winding Power Transformer With NVTC/OLTC | ||||||||
Rated Capacity (kVA) | Rated Voltage (kV) | Vector Group | Losses (W) | Impedance Voltage (%) | ||||
HV | Tapping Range | LV | No load | On load | Step Up | Step Down | ||
6300 | 110 ±2×2.5% 121 ±2×2.5% | 35 38.5 ±2×2.5% | 6.3 6.6 10.5 11 | YNyn0d11 | 9600 | 47700 | HV-MV 17-18 HV-LV 10.5 MV-LV 6.5 | HV-MV 10.5 HV-LV 17-18 MV-LV 6.5 |
8000 | 11500 | 56700 | ||||||
10000 | 13600 | 66600 | ||||||
12500 | 16000 | 78300 | ||||||
16000 | 19300 | 95400 | ||||||
20000 | 22800 | 112500 | ||||||
25000 | 27000 | 133200 | ||||||
31500 | 32000 | 157500 | ||||||
40000 | 38200 | 189000 | ||||||
50000 | 45200 | 225000 | ||||||
63000 | 53600 | 270000 |
Nominal system voltage
(kV, rms) | Highest system voltage
(kV, rms) | Lightning Impulse withstand voltage, dry (kV, peak) | Power frequency withstand voltage, wet (kV, rms) |
33 | 36 | 200 | 95 |
132 | 145 | 650/750 (internal/external) | 275/325(internal/external) |
Product Categories : Distribution Transformers > 66,110,220kV Distribution Transformers