Product Description

Specifications FN12-12 Series Indoor High Volgate Break Switch

1 ISO9001

2 12kV 50HZ

3 Safty,Perfect,Loss energy loss

4 Manufacturer

Indoor 12kV/24kV/36kV  Load Break Switch  FN12-12D and FN12-12DRSwitchgear is a rated voltage of 12kV, rated frequency 50Hz three-phase high-voltage Switchgear for the division and load current, Loop current, no load Transformer and cable charging current, short circuit current of the Closing, Fuse may short-circuit breaking current, with equipment grounding switch load switch that can withstand short-circuit current, mainly for three-phase power s../upply ring network city distribution and industrial power equipment for load control and short circuit protection.   Using condition a.ambient temperature -25oC-+40oC b.elevation≤1000m c.humidity:daily average humidity≤95%,monthly≤90% d.the earthquake does not exceed degree 8 e.no fire,explsion,chemical errosion.. f.pollution:level 2     Main technical parameters

Serial number

Project

Unit

FN12-12/630

FNR12-12/100-31.5

1

Rated Voltage

kV

12

2

Rated Frequency

HZ

50

3

Rated Current

A

630

1250

4

Lightning impulse withstand voltage

kV

On the ground and 75 isolation facture85

5

1min Frequency withstand voltage

kV

42 on the ground and white, isolated facture48

6

Rate thermal current

kA

20(4S)

7

Rated dynamic current

kA

50

8

Rated shot circuit making current(peak)

kA

50

9

Rated short-circuit breaking current(project)

kA

31.5

10

Rated transfer current

kA

1.5

11

Operating Agency

KVA

1250

12

Rated cable charging current

A

10

13

Mechanical life

Times

4000

14

Fuse switches gate trigger load time

S

<0.06

15

Ground thermal current switch

kA

20(4s)

16

Grounding switch dynamic current(peak)

kA

50

  Dimension drawing          

Contact us if you need more details on Air Load Break Switch. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Air Load Break Switch、Air Load Break Switch. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Circuit Breakers & Switches > Load Break Switch